These high performance, network compatible paperless recorders incorporate a high visibility 5.7" TFT touch panel color LCD and are available with 6, 9 or 12 universal channels. They combine a high speed sampling rate of 100 ms for 12 points with an accuracy of ±0.1%. Measured data is stored either in internal flash memory or in a 2GB SD or 32GB SDHC card. Data can be monitored by a web browser on internet or intranet with FTP transfer of data files. The recorder can be used for various applications such as data management, research, development etc. and a wide range of monitoring options is available by utilizing the internet environment.
- Touch Panel 5.7” TFT Screen
- Inputs: Thermocouple Types K, T, J, N, R, S, B, L, U, C and Pt100, DC Voltage and DC Current
- 6, 9 or 12 channels
- PC Support software included
- Multi point recording with high speed and accuracy
- Easy Operating and Programming without manuals
- LAN Network plus FTP to internet capability
- Large capacity storage by SD/SDHC card
- IP65 Rated
Specifications:
Measuring cycle: 100ms
Recording cycle: 1sec to 60mins (main/sub record, 100ms can be selected at sub record)
Indication accuracy: ±0.1%+1digit of input range
Burnout: Disconnection of thermocouple and RTD input; UP/DOWN selectable
Digital Filter: Range/Scale is selectable when DC voltage/current is programmed
Memory: 128MB Flash memory, CF card, 2GB SD and 32GB SDHC capacity
Recording cycle: adjustable between 1second to 60 minutes
Logging Data: Measured data; file name (group name), time of day, month and year of recording start, tag, measured data, alarm status/types Stored on Binary/CSV file
Operating Conditions: 0 to 50°C, 20 to 80% RH
Power Voltage: 85 to 264 Vac 50/60 Hz ±1%
Dimensions: 150mm x 144mm x 208mm
Display Specifications:
Display: 5.7” TFT QVGA Touch Panel colour LCD
Measured Data Display: Trend display, digital display, bar-graph display
Trend Screen: 16 colors vertical or horizontal (selectable)
Display Points: Maximum 12 points/screen
Alarm Display: Alarm activation/released history display Marker List
Alarm Specifications:
Setups: Up to 4 alarms can be programmed per channel
Alarm Types: Upper limit, lower limit, abnormal data
Ethernet Specifications:
FTP Server: Download and delete of the record file saved in SD memory. Data file can be read from the network computer with the software supplied with the recorder
HTTP Web Server: Measured-value display and alarm condition of each channel by browser
Modbus TCP: Data read in/write of setting out is possible at a Modbus TCP protocol